Dry Type Transformer

Dry Type Transformer | Cast Resin & Prepreg Technology |50–6300kVA | ZTelec

ZTelec high-performance dry type transformers from 50 kVA to 6300 kVA, up to 36 kV. Eco-friendly, fire-safe, moisture-resistant, and ideal for commercial, industrial, and infrastructure applications. Learn about epoxy cast and prepreg resin technology

Product Overview

Dry type transformers differ from oil-immersed transformers primarily in their cooling method. The high-voltage windings are vacuum cast with epoxy resin, while the low-voltage windings are manufactured using either cast resin or resin-impregnated prepreg technology, ensuring high reliability in various environmental conditions.

Cooling methods include natural air cooling (AN) and forced air cooling (AF). With fan-assisted cooling, the transformer can achieve up to 40% increased load capacity.

Power range: 50 kVA to 6300 kVA

Voltage level: Up to 35 kV

Key Features

Environmentally Friendly: Oil-free design eliminates the risk of leakage and environmental pollution.

Fire Safety: Flame-retardant epoxy resin minimizes fire hazards.

Moisture Resistant: Can be put into service immediately even after long periods of inactivity; ideal for humid or dusty environments.

Low Maintenance: Compact and robust structure requires minimal upkeep.

Enhanced Cooling: Optional fan cooling allows over 40% load increase.

Versatile Applications: Widely used in high-rise buildings, commercial centers, rail transit, hospitals, and airports—especially where fire safety and eco-compliance are essential.

Implementation standards

GB 1094 : Power Transformer

IEC 60076: Power Transformer

GB/T10228 :Specification and Technical Requirements of Dry type Power Transformers

JB/T10008 :6kV-500kV Power Transformer Sound Level

GB/T7354 : Partial Discharge Measurements

Application

The product is widely used in power transmission and transformation systems,such as hotels,restaurants,airports,high-rise buildings, commercial centers,residential quarters and other important places,as well as subways,smelting power plants and other harsh environments.

ZTelec Dry Type Transformer Installation

Technical Parameters

Rated capacity (kVA) Voltagegroup Impedance voltage(%) SC(B)10 Sound leve (dB) Dimension(mm) Weight(kg)
HV(kV) Tap range LV(kV) No-loadloss (W) Loadloss120℃ (W) No-load curren (%) L W H
30 10 11 10.5 6.6 6.3 6 ±2×2.5% ±5% 0.4 4 190 710 2.0 44 620 400 600 220
50 270 1000 2.0 44 650 400 740 320
80 370 1380 1.5 45 750 500 770 460
100 400 1570 1.5 45 800 500 830 580
125 470 1850 1.3 46 950 880 1090 750
160 540 2130 1.3 46 950 880 1090 780
200 620 2530 1.1 47 1050 900 1200 850
250 720 2760 1.1 48 1050 900 1200 1030
315 880 3470 1.0 48 1080 900 1250 1060
400 980 3990 1.0 49 1110 950 1270 1400
500 1160 4880 1.0 49 1130 950 1380 1550
630 1340 5880 0.85 49 1200 950 1450 1820
630 6 1300 5960 0.85 50 1320 950 1375 1850
800 1520 6960 0.85 51 1310 1000 1315 2150
1000 1770 8130 0.85 52 1400 1070 1520 2550
1250 2090 9690 0.85 53 1440 1150 1570 3020
1600 2450 11730 0.85 54 1650 1200 1795 4500
2000 3050 14450 0.7 55 1800 1260 1870 5300
2500 3600 17170 0.7 56 1950 1260 2035 6200
Rated capacity (kVA) Voltagegroup mpedance voltage(%) SC(B)11 Sound eve (dB) Dimension(mm) Weight(kg)
HV(kV) Tap range LV(kV) No-loadloss (W) Loadloss120℃ (W) No-load current (%) L W H
30 10 11 10.5 6.6 6.3 6 ±2×2.5% ±5% 0.4 4 170 710 2.0 44 620 400 600 220
50 250 1000 2.0 44 650 400 740 320
80 330 1380 1.5 45 750 500 770 460
100 360 1570 1.5 45 800 500 830 580
125 420 1850 1.3 46 950 880 1090 750
160 490 2130 1.3 46 950 880 1090 780
200 560 2530 1.1 47 1050 900 1200 850
250 650 2760 1.1 48 1050 900 1200 1030
315 790 3470 1.0 48 1080 900 1250 1060
400 880 3990 1.0 49 1110 950 1270 1400
500 1040 4880 1.0 49 1130 950 1380 1550
630 1210 5880 0.85 49 1200 950 1450 1820
630 6 1170 5960 0.85 50 1320 950 1375 1850
800 1370 6960 0.85 51 1310 1000 1315 2150
1000 1590 8130 0.85 52 1400 1070 1520 2550
1250 1880 9690 0.85 53 1440 1150 1570 3020
1600 2210 11730 0.85 54 1650 1200 1795 4500
2000 2750 14450 0.7 55 1800 1260 1870 5300
2500 3240 17170 0.7 56 1950 1260 2035 6200

Product Details

FAQ

1. What certificates do your transformers have?
CE, ISO, Test certificates.
2. What is the capacity of the transformers you provide?
50-20000kva. We can provide customized services for various transformers within the range!
3. How long is the warranty period of the transformer?
We provide a 12-month warranty period.
4. How long is the delivery time and delivery time of the transformer?
After receiving the advance payment, the production cycle is 15-25 days. The transportation cycle should be calculated according to your region and mode of transportation.
5. Which countries do you export your products to?
We support global supply, and our products have been exported to more than 60 countries, Southeast Asia, the Middle East, South America, Africa, Americas
 
 

leave message to us!

read moreyou may like:
Polyimide glass fiber sheet PIG

Polyimide glass fiber sheet PIG

FR4 Epoxy Fiberglass Sheet

FR4 Epoxy Fiberglass Sheet

EPGC 308 Epoxy Fiberglass Board

EPGC 308 Epoxy Fiberglass Board

NMN 6640 NOMEX Mylar Paper

NMN 6640 NOMEX Mylar Paper